Sensor Mod.
|
CHB-40KA Closed-loop Hall Current Transducer
|
|
Description
|
The SENSOR Module CHB-40KA is a closed loop Hall current sensor to measure 40,000A DC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits. The aperture can be opened by a structure of a split core for easy installation.
|
|
|
|
Closed-loop Hall Current Sensor:
|
|
Type
|
Nominal current
|
Output current
|
Accuracy
|
Supply voltage
|
Aperture
|
|
IN(A)
|
IM(mA)
|
X(%)
|
Vc(V)
|
mm
|
|
CHB-40KA
|
40,000
|
8,000
|
±0.4%
|
±36~48
|
162x188
|
|
|
|
Specifications:
|
|
Principle
|
Closed loop Hall effect principle
|
|
Input current
|
40,000A(DC、AC、Pulsed current)
|
|
Output current
|
8000mA
|
|
Turns ratio
|
1:5000
|
|
Frequency
|
DC~20KHz
|
|
Accuracy
|
±0.4%
|
|
Response time
|
<1μS
|
|
Linearity
|
<0.1%
|
|
Supply voltage
|
±36V…48V(±5%)
|
|
Consumption
|
60mA+IM(Output current)
|
|
Isolation voltage
|
Between primary and secondary circuit: 10KV RMS/50Hz/1min.
|
|
Operating temp.
|
-25 …+70℃
|
|
Applications
|
The sensors are used in the industry field of power supplies, welding machines, converters,
|
|
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc.
|
|
|
|
Dimensions(mm) & Connection:
|
|
|
|
|
|
Typical Applications:
|
|
|