DTP300 Electrical Fire Monitoring
Mainly used in the low-pressure three-phase four-wire system leakage protection and realize the main basic U, I, P, KWH and isoelectric parameter display; LCD display, data turns display and designated show optional; With time memory function, alarm can record 50 fault happen type, time, departure time values, according to the fault record can analyse the reason of failures to provide basis for the elimination of failure.
Use range
1.Apply to all kinds of existing electrical equipment
2.High-rise buildings, fire hazard in places such as crowded conditions of electrical protection
3.Key fire-proof building electrical protection
4.Electrical parameters of time measurement
5.Electrical fire monitoring system
6.Suitable for 380V voltage grade palaces line protection
Professional design
■Professional independent design, powerful, reveal the technical strength
■Industrial parts, stable and reliable, the first-class quality
■Through the national fire protection test
■Series is complete multiple types can be chosen
■Applicable to 0.4 KV electric voltage grade fire monitoring protection
■Work into electricity switching power supply, work straight and wide range
DTP300 series product main function
◆LCD display, data turns display and specified display can be chosen
◆Has the leakage, temperature, pressure, undervoltage etc. Various protection function
◆To achieve the three-phase voltages, the power supply line, power, the three phasecurrent high-power electric parameters such as electric degrees, the measurement
◆Provide four lk switch input, programmable trigger events, can set with fire smoke sensors, remote signal connection, constitute fire linkage
◆Adopt fieldbus communication technology, PC management software can real-time monitoring each detector. Communication with RS485, this communication system reliability, expansibility, using international standards of Modbus - RTU agreement, can with all sorts of standard power monitoring software connected
◆With time memory function, alarm can record 50 fault happen type, time, triggering time values, according to the fault record can analyse the reason of failures to provide basis for the elimination of failure
Performance
|
Environmental conditions |
|
Working temperature The subject :-20℃~+50℃ |
|
Liquid crystal display (LCD) : -10℃~50℃ |
|
Storage temperature -20℃~85℃ |
|
Relative humidity ≤95% |
|
The altitude ≤2000m |
|
Degree of protection IEC529IP52 |
|
Working power supply |
|
Ac voltage 85~265VAC |
|
The power frequency 45~65Hz |
|
Dc voltage 100~300VDC |
|
Power consumption ≤2VA |
|
Communication RS485 |
|
Interface Modbus-RTU |
|
Communication protocol 2400~9600 |
|
Electromagnetic compatibility standards |
|
Electrostatic resistance test IEC61000-4-2 |
|
Radiation immunity test IEC6100-4-3 |
|
Conduction rf interference test EN55022,ClassB |
|
Transient pulse test IEC61000-4-4,Level3 |
|
Surge immunity test EC61000-4-5,Level3 |
|
Radio frequency radiation interference test EN55022,ClassB |
|
Rated current level (A) 16、25、32、40、50、63、80、100、 |
|
125、140、160、180、200、225、 |
|
250、315、400、630、800、1250 |
|
The rated voltage (V) Three phase four wire, phase voltage AC220V |
|
Residual current measuring range 0~1000mA |
|
Residual current setting value l△ 50~1000mAStep selection, each interval 50mA |
|
Forecasting warning value l△no(mA) l△no=1/2 l△n |
|
The action time (S) 0.1~5adjustable ,interval 0.1S |
|
Over-voltage action (V) 120~150%The rated voltage |
|
Voltage under-voltage action (V) 60~80%The rated voltage |
|
Temperature measurement : 10~150℃,action :55~140℃ |
|
Overall dimensions DTP300:Length X width X height (mm)144X90X57 |
|
DTP300B:Length X width X height (mm)96X96X55 |
|
DTP300C:Length X width X height (mm)72X72X74 |
Selection Guide
|
Category |
Single multi-function series
|
Multi-channel series |
economy
|
||||||
|
Function
|
DTP300
|
DTP301
|
DTP302
|
DTP303
|
DTP310
|
DTP311
|
DTP300B
|
DTP300C
|
|
|
Real-time measuring value
|
Phase voltage
|
—
|
—
|
■
|
■
|
—
|
—
|
—
|
—
|
|
current
|
■
|
■
|
■
|
■
|
—
|
—
|
—
|
—
|
|
|
Residual current
|
■
|
■
|
■
|
■
|
—
|
—
|
—
|
■
|
|
|
Environment temperature
|
—
|
—
|
■
|
■
|
—
|
—
|
—
|
*
|
|
|
Total have power
|
—
|
—
|
—
|
■
|
—
|
—
|
—
|
—
|
|
|
Meritorious electric degrees
|
—
|
—
|
—
|
■
|
—
|
—
|
—
|
—
|
|
|
Protection function |
Leakage protection
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
|
Over-current protection
|
—
|
■
|
■
|
■
|
—
|
—
|
—
|
—
|
|
|
Temperature protection
|
—
|
■
|
■
|
■
|
—
|
—
|
*
|
*
|
|
|
Over/owe protection
|
—
|
—
|
■
|
■
|
—
|
—
|
—
|
—
|
|
|
Phase lack protection
|
—
|
—
|
■
|
■
|
—
|
—
|
—
|
—
|
|
|
Event record
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
|
|
Voice alarm
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
|
|
Self-check function
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
|
|
Expansion function |
Smoke detection
(S) |
—
|
*2
|
*2
|
*2
|
—
|
—
|
—
|
—
|
|
Consumption linkage (F)
|
*1
|
*1
|
*1
|
*1
|
*1
|
*1
|
*1
|
*1
|
|
|
Alarm output (P)
|
*1
|
*1
|
*1
|
*1
|
*1
|
*1
|
*2
|
*1
|
|
|
Are dctection(A)
|
*
|
*
|
*
|
*
|
— | — | — |
—
|
|
|
Communication
|
RS485communication
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
■
|
|
Leakage circuit
|
|
1
|
1
|
1
|
1
|
4
|
8
|
12
|
1
|
“■” intrinsic function, "*" optional function, "-" no this function