Three-phase power meter ME631
Connectivity advantages
| MODEL | ME631P22 | ME632P12 |
| Support Extra sensor | 333mV CT Rogowski coil |
|
| Programmable digital output | Alarm Relay |
Alarm 4 Tariff |
| I/O function | 1*digital output | 2*digital output 2*digital input |
| Power | 85~265V AC/DC | 12VDC |
| Option | 1GB SD card option (save intervals 10mins) |
|
Application
Network measurement
Specification
Specification
| Model | ME631P22 | ||
| Product component type | Multifunction power meter | ||
| Poles description | A: 3PH4W 1PH2W (L-N) 1PH3W(L-L-N) B: 3PH3W 1PH2W(L-L) |
||
| Device application | Power analysis Tariff meter |
||
| Input type | External CT(333mV only) Rogowski coil |
||
| Display | 2.0 inch TFT screen display | ||
| Sampling rate | 8k samples per second | ||
| Mounting mode | Clip-on | ||
| Mounting support | DIN rail | ||
| Harmonic | 52th Max | ||
| Display characteristics | |||
| Dimensions (VA) | 39mm x 32mm | ||
| Display resolution | 220 x 170 dots | ||
| Mechanical characteristics | |||
| Weight | 212g | ||
| Dimension | L*W*D:76*95*71mm | ||
| Maximum value measured | ||
| Parameter | Range | Resolution |
| Voltage | 9999.9V | 0.1 |
| Current | 9999.9A | 0.1 |
| Power | 9999kW | 0.001 |
| Power factor | 0.999 | 0.001 |
| THD | 99.9% | 0.1% |
| Energy | 9999.9KWH 999.99MKWH |
0.1KWH 0.01MKWH |
| Instantaneous rms Values | |
| Voltage | U,UTH2,UTH3,UTH4(Per Phase,AVG) |
| Current | I,ITHD2,ITHD3,ITHD4(Per Phase,AVG) |
| Power | P,FQ,S,PF(Per Phase,AVG) |
| Energy | EP,EFQ,ES,Freq(Per Phase,SUM) |
| UTHD(%) | UTHD,THD2,THD3,THD4(Per Phase,AVG) |
| ITHD(%) | ITHD,THD2,THD3,THD4(Per Phase,AVG) |
| Update rate | |
| Data acquisition rate | 400ms |
| Display update rate | 0.5s |
| Calibration | |
| Current | Per phase,all |
| Voltage | Per phase,all |
| Power factor | Per phase,all |
| Energy | Reset to “0” |
| Measurement accuracy | |
| Current | 0.5% from 10% to 120% |
| Voltage | 0.2% from 50V to 360V (Ph-N), from 80V to 620V (Ph-Ph) |
| Power factor | ±0.005 from 10% to 120% |
| Active/Apparent Power | IEC62053-22 Class 0.2 |
| Reactive power | IEC62053-21 Class 2 |
| Frequency | 0.01% from 45 to 65Hz |
| Active energy | IEC62053-22 Class 0.2s |
| Reactive energy | IEC62053-21 Class 2 |
| Measurement arrange | |
| Measured voltage | 50V to 360V AC (direct Ph-N) 80V to 620V AC (direct Ph-Ph) |
| Frequency range | 45Hz to 65Hz |
| Input-current characteristics | |
| Primary current range | Adjustable from 0.1A to 9999A |
| Measurement input range | 1/225mV-333mV |
| Permissible overload | 600mV for 10s/hours |
| Control Power | |
| AC | 85 to 265VAC (+/-0%), 3W/5VA; 45Hz to 65Hz |
| DC | 85 to 265VDC, 3W |
| Output | |
| Digital output | 1×digital output(3 ports),relay,rated 24V/800mA, 75mΩmax, 2.5kVrms insulation |
| Wire diameter for terminals | |
| Connections-terminals | Screw terminals 2.5mm2,interval 5.08mm |
| Alarm | |
| Setting | Each phase,AVG |
| Output form | Buzzing or Relay |
| Alarm Option | Overvoltage,overcurrent,low current,low voltage |